| Zellspezifikation | LFP, 3.2 V / 280 Ah |
|---|
| DC-Spannungsbereich | 728-940 V | 1,164-1,500 V |
|---|
| Batteriepack-Energie | 46.592 kWh |
|---|
| Batteriesystem-Energie | 232 kWh | 372 kWh |
|---|
| Batteriepack-/DC-Schutz | IP67; circuit-breaker DC protection |
|---|
| AC-Nenn-/Maximalleistung | 100 / 120 kW | 200 / 240 kW |
|---|
| AC-Spannung/Frequenz | 380 V; 50 Hz |
|---|
| Netzqualität | < 3% THD; power factor > 0.99 above 20% load |
|---|
| Systemwirkungsgrad | ≥ 89% excluding auxiliary consumption |
|---|
| Lade-/Entladeleistung | ≤ 0.5C; 0-99% DOD; > 10,000 cycles at 70% |
|---|
| Betriebsbedingungen | -30 to 50 °C; 0-95% RH without condensation; altitude up to 4,000 m with derating above 2,000 m |
|---|
| Brandlöschung/Kühlung | Water cooling; active early warning, aerosol and perfluorohexanone fire protection |
|---|
| Kommunikation/Schutz | RS485, CAN and Ethernet; IP54 system protection |
|---|
| Abmessungen | 1,300 × 2,465 × 1,350 mm |
|---|
| Gewicht | 2,600 kg | 4,900 kg |
|---|