| Zellspezifikation | LFP, 3.2 V / 280 Ah |
|---|
| DC-Spannungsbereich | 600-876 V |
|---|
| Batteriepack-/Systemenergie | 46 kWh pack; 1,200 kWh system |
|---|
| Batteriepack-/DC-Schutz | IP65; circuit-breaker DC protection |
|---|
| AC-Nenn-/Maximalleistung | 300 kW (5 × 60 kW charging points); 330 kW maximum |
|---|
| AC-Spannung/Frequenz | 380 V; 50/60 Hz |
|---|
| Netzqualität | < 3% THD; power factor > 0.99 above 20% load |
|---|
| Systemwirkungsgrad | ≥ 89% excluding auxiliary consumption |
|---|
| Lade-/Entladeleistung | ≤ 0.5C; 0-95% DOD; > 8,000 cycles at 70% |
|---|
| Betriebsbedingungen | -20 to 50 °C; 0-95% RH without condensation; altitude up to 3,000 m with derating above 2,000 m |
|---|
| Brandschutz | Active early warning, aerosol and perfluorohexanone |
|---|
| Kommunikation/Schutz | RS485, CAN and Ethernet; IP54 system protection |
|---|
| Abmessungen | 6,058 × 2,791 × 2,438 mm |
|---|
| Gewicht | 16,000 kg |
|---|